Digital Controller

Before we get started, please learn that what we’re going to talk about is the fan nearby the evaporator, for the purpose of pushing cold air into the storage room. It is not the fan nearby the condenser or another blower nearby the compressor.

Both the STC-2304 and STC-9200 defrost thermostat offer 3 output relays for controlling refrigeration, evaporator defrosting, and evaporator Fan, then which one is the best temperature controller for cold storage room? Which one should you take?

Difference in Specification

From the below table, you will find that

  • The controllable range of STC-2304 is from -40 to 85°C, it adopts a modern touch-sensitive key, and offers more Time delay options;
  • On the other hand, STC-9200 from -50 to 50 Celsius degree, uses the normal press button, but with a copy-key port on the back panel.
Tips: Slide left and right to see more columns if more than 5 Products.
Sku
Price
Title
Function
Thermostat Types
Main Function
Time Delay
Sensor & Cable
Alarm Temperature
Alarm Methods
Temp. Range
Measure Min
Measure Max
Control Min
Control Max
Front Panel
Resolution
Interactive Mode
Front Size (W*H)
Mounting (W*H)
STC-2304
EXW: $13.23$14.53
 
Programmable Thermostat
3 Relays, Refrigeration + Defrost + Fan
Compressor Delay - Editable, Alarm Delay - Editable, Alarm Delay - Editable - 1st Time Boot, Fan Delay - Editable, Fan Delay - Editable - 1st Time Boot
2PCS, 10K, 2m Cable, replaceable
Editable
Audible, Visible
 
-40℃
99.9℃
-40℃
85℃
 
0.1℃ Resolution
Touching Sensitive Button
85*35mm
71*29 mm
STC-9200
EXW: $11.94$13.23
 
Programmable Thermostat
3 Relays, Refrigeration + Defrost + Fan
Compressor Delay - Editable, Alarm Delay - Editable, Fan Delay - Editable
2PCS, 10K, 2m Cable, replaceable
Editable
Audible, Visible
 
-50℃
50℃
-50℃
50℃
 
0.1℃ Resolution
Copykey - Mini USB, Push Button
75*34 mm
71*29 mm

Function Menu & Parameters Comparison

More difference among of them in details, let’s compare it from the function menu list.

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 1SETF1SP (Temperature Set-Point)ON TEMPCompressor Starts Temperature
HYF2Temperature HysteresisOFF TEMPCompressor Stops Temperature
USF3Upper limit of SP could reach
LSF4Lower limit of SP could reach
Block 2ACF5Compressor Delay TimeF9Compressor Delay Time
1 DFF6Defrost Cycle / Interval TimeF2Defrost Cycle / Interval Time
MDFF7Defrost Lasting TimeF1Defrost Lasting Time
DTEF8Defrost Stop TemperatureF6Defrost Stop Temperature
Block 3FDTF9Water dripping Time after DefrostF4Water dripping Time after Defrost
F8Time delay for fan 1st time running after pass F4
Block 4TDFF10Defrosting by
EL: Electrical-heating,
HTG: Thermal Air
F5Defrosting by,
0 = Electric-Thermal,
1 = Hot Air,
2 = Wind
Block 5DCTF11Count mode of defrost cycle:
RT: Cumulative time from controller power on;
COH: Cumulative time of compressor working.
F3Count mode of defrost cycle:
0: Cumulative time from controller power on;
1: Cumulative time of compressor working.
Block 6DFDF12Display mode when defrosting:
RT: Show Room sensor temperature;
IT: show defrost sensor temperature (lasting 10m after defrosting over)
Block 7FNCF13evaporator Fan output options:
CTR: Fan Starts by F14/FOT, Stop by F16/FST;
O-N: continuous operation except defrosting begin;
C-N: Fan start-up later than the compressor (FOD/F15), Stop if defrost begins.
FOTF14Defrost sensor Temperature for Fan Starts
FODF15Time delay seconds for evaporation Fan:
FOD < 0 Fan start-up earlier than the compressor (FOD/F15) seconds;
FOD ≥0, controller by F13/FNC.
F7evaporation Fan modes:
<0, earlier than the compressor start;
=0, synchronous with the compressor;
>0, later than the compressor starts;
C: continuous working without interval;
D: continuous working except defrosting time.
FSTF16Defrost sensor Temperature for Fan Stops
Block 8ALUF17Room Sensor Temp. (Not Over-Temp.) to Trigger AlarmUpper LimitF11Room sensor Over-Temperature Value to Trigger Alarm
ALLF18Lower Limit
ALDF19Time delayF10Room Temp. Alarm Delay Time for 1st time power on
F12Room Temp. Alarm Delay Time after time pass F10
Block 9OTF20Temp. Calibration = Real Temp.-Measured Temp.F13Temp. Calibration = Real Temp.-Measured Temp.

There are 8 blocks:

Block 1, Set the Controlling Temperature Range

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 1SETF1SP (Temperature Set-Point)ON TEMPthe compressor Starts Temperature
HYF2Temperature HysteresisOFF TEMPthe compressor Stops Temperature
USF3Upper limit of SP could reachN/AN/A
LSF4Lower limit of SP could reachN/AN/A

  1. STC-2304 is a high low limit temperature controller which means the suitable temperature range determined by an upper limit (on temp) and a lower limit (off temp);
  2. STC-9200 utilizes the temperature set-point and Temperature Hysteresis value to carry out the same purpose;

Block 2, Compressor delay time and the defrosting timing setting.

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 2ACF5the compressor Delay TimeF9the compressor Delay Time
1 DFF6Defrost Cycle / Interval TimeF2Defrost Cycle / Interval Time
MDFF7Defrost Lasting TimeF1Defrost Lasting Time
DTEF8Defrost Stop TemperatureF6Defrost Stop Temperature
totally the same, no more words here.

Block 3, Water Dripping Time after Thawing

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 3FDTF9Water dripping Time after DefrostF4Water dripping Time after Defrost
N/AN/AN/AN/AF8Time delay for evaporator fan 1st time running after pass F4
  • STC-2304 exist two parameters related to Room Temp. Alarm Delay Time, F10 is for the first time power on, and F12 for the rest of time after F10 overs.
  • STC-9200 just owns one delay time F19, you can press any key to stop the annoying screaming, however, the display still shows an error code before air temperature cold down.

Block 4, Defrosting Methods

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 4TDFF10Defrosting by
EL: Electrical-heating,
HTG: Thermal Air
F5Defrosting by,
0 = Electric-Thermal,
1 = Hot Air,
2 = Wind
  • Both of them offer the electrical-heating and thermal gas from the compressor reversal rolling.
  • STC-2304 exist one more option, that is defrosting by the wind from the fan, it is a kind of internal recycling.

Block 5 Timing mode of defrost cycle

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 5DCTF11Count mode of defrost cycle:
RT: Cumulative time from controller power on;
COH: Cumulative time of the compressor working.
F3Count mode of defrost cycle:
0: Cumulative time from controller power on;
1: Cumulative time of the compressor working.
Both of them offer two methods for counting time, and they are the same.

Block 6, What is the temperature Value on the Screen?

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 6DFDF12Display mode when defrosting:
RT: Show Room sensor temperature;
IT: show defrost sensor temperature (lasting 10m after defrosting over)
N/AN/A
STC-9200 allows shows the evaporator temperature instead of storage room temperature by setting the DFD/F12. STC-2304 without this function, the user must hold the “UP” Key for 3s to check the defrost temp after unlocking keys.

Block 7, Fan Working Mode and Time

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 7FNCF13evaporator Fan output options:
CTR: Fan Starts by F14/FOT, Stop by F16/FST;
O-N: continuous operation except defrosting begin;
C-N: Fan start-up later than the compressor (FOD/F15), Stop if defrost begins.
N/AN/A
FOTF14Defrost sensor Temperature for Fan StartsN/AN/A
FODF15Time delay seconds for evaporation Fan:
FOD < 0 Fan start-up earlier than the compressor (FOD/F15) seconds;
FOD ≥0, controller by F13/FNC.
F7evaporation Fan modes:
<0, earlier than the compressor start;
=0, synchronous with the compressor;
>0, later than the compressor starts;
C: continuous working without interval;
D: continuous working except defrosting time.
FSTF16Defrost sensor Temperature for Fan StopsN/AN/A
From the above part,
  • STC-9200 starts and stops the refrigerator evaporator fan by the time or the defrost sensor temperature (F14, F16), with it the freezer fan will not always running, just working when necessary;
  • STC-2304 just can controls the evaporator fan by time, without the temperature condition.

When does the evaporator fan turns on or off?

This simple question with a complicated answer, because each of the above evaporator fan controllers offers multi-plans for the fan.
  • If you want the evaporator fan is always run, only the SCT-2304 is ok, because when the F7 = C, the fan will ignore the defrost status.
  • But if you like the fan stops working during the defrosting time, both of them are ok.
  • we’ve marked the same function with the same color in the above comparison table, we believe you could understand it easily.

How to set the Defrost termination/fan delay?

After the defrost over, assume the instant time have passed the compressor delay time, the refrigerator starts
  • STC-9200,
    • firstly, Set the fan delay time in FOD/F15 ( should > 0, assume it is 5min)
    • Next set the F13 = C-N, the fan will delay 5 mins before startup.
  • STC-2304,
    • Just set the F7 = 1 or a larger number, you’ve finished the configuration.
There is no strange method in the wiring diagram of these defrost fan controller, the key is to understand the menu list and manual.

Block 8, Alarm Room Temperature

BlocksSTC-9200STC-2304
EN CodeF CodeFunctionCodeFunction
Block 8ALUF17Room Sensor Temp. (Not Over-Temp.) to Trigger AlarmUpper LimitF11Room sensor Over-Temperature Value to Trigger Alarm
ALLF18Lower LimitN/AN/A
ALDF19Time delayF10Room Temp. Alarm Delay Time for 1st time power on
N/AN/AN/AN/AF12Room Temp. Alarm Delay Time after time pass F10
both of them could trigger the alarming function once the temperature exceeds the safe range, but there is a little difference:
  • STC-9200 offers separately “low limit and high limit temperature value” to define alarm point, the advantage is these two value could be different, and need not to plus or minus other data.
  • STC-2304 just supply one Over-Temperature value to set the silence range out of which will trigger alarming, the micro-computer inside will calculate the upper limit ( the OnTemp Value + the Over Temp Value), and the lower limit ( The Off Temp Value – the Over Temp Value); yet, it offers a sweety option namely “Room Temp. Alarm Delay Time” for 1st-time boot.

The Difference Part in Wiring Diagram

2020 New Wiring Diagram of Digital temperature controller STC 9200 from Haswill Electronics
STC 2304 digital temperature controller wiring diagram

Conclusion

The max current is different; Both of them support forced-defrosting manually; Both of them alarm through the error code on display and buzzer screams, but without alarm output like STC-9100;

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

STC-9200 Evaporator Defrost & Fan Controller

  • It offers a wider controllable range, owns press-type buttons;
  • could show the defrosting sensor temperature instead of room temperature on the display;
  • Regulates the evaporative cooling fan by time and temperature;
  • separately user menu and admin menu;
  • A Mini-SUB port on the back panel, Batch upload configuration data by USB-Disk is achievable, save time if you have a lot of walk-in cold storage rooms.

STC-2304 Evaporator Defrost & Fan Controller

  • The STC-2304 fan regulating thermostat control from -50°C ~ 50°C;
  • owns touch-sensitive keys;
  • offers friendly options of time delay for the 1st-time power on;
  • controls the evaporator fan only by time;
  • shortcut key to set the suitable temperature range, and auto-lock the keys to preventing mistakenly touching.

Showing all 2 results