STC-9200 digitalis defrost thermostat disposito ad regendum Refrigeration & Evaporator Defrost & Evaporator Fan potentia copia status per 3 output dispositos et 2 NTC sensoriis. Typice aptatur ad conclavia freezer quae opus est ad effectum evaporatorem moderandum et frigidus editi.?
Minimum ordo moles: CC USD
Voltage
Quoad intentionem huius moderatoris electronici caliditatis
- 220V AC (± 15%) ut defaltam, Sine MOQ exigentiam ordinis minimam;
- 110V AC (± 15%) cum MOQ CC PCS;
- 12V DC cum MOQ CC PCS;
- 24v dc Sine MOQ postulatione;
STC-9200 Defrost Thermostat Features
- Temperamentum paro-punctum (-50 .0 ad 500.0 ) et hysteresis est ut scopum temperatum range determinare; Maximum autem et humile limitem ad Temperaturae Set-punctum praesto est;
- Tempera refrigerationem per temperiem et moras tempus editabile;
- Temperantia et mora editable temperie defrosting per tempus, et artificiosa coacta defrost praesto;
- Supple aqua fluens tempus editabile;
- Duo temporis optiones numerant modum cycli defrosting;
- Defrost sensorem temperatura permanentem ostensionem ostensionis est rem deduceretur;
- Trepidatio per errorem codicis in ostentatione et stridore clamoribus, et super- temperaturae functionis terrorem debilitatum esse potest;
- Temperatus terrorem moderari freezer locus per tempus et temperies;
- Temperature ventilabrum per Tempus & Temperature.
Features 1 ad 8 sicut idem quod STC-9100 defrost temp controller; pluma 9 eft circa ventilabrum imperium.

STC-9200 temperatus moderatoris Benefits
- Multiplices modos operantes pro ventilabro evaporatore, plures missiones operiunt;
- Separatim administrator et menus usorum, facile sunt operari pro usoribus, et punctum praefixum limitari in menu lockable admin;
- Coactus REFRIGERATIO & coactus defrosting manually praesto sunt;
- Optiones sufficiens ad occasus defrosting, sicut aqua destillans Tempus, tempus diutinum defringens, temporis intervallum defrosting, Desine Temperature Defrosting, et modum defrost cycli Comitis.
- Batch upload/download configure data ad gubernatrix subsidium per Exemplar-Key;
- Magna et clara DUXERIT ostensio cum resolutione 0.1°C;
- 2 frusta IMPERVIUS NTC sensorem temperatura (2 m longitudo funis sensoris) cum accuratione ±1°C;
Elitech STC-9200 Temperature controller Front Panel
Quattuor claves in tabula anteriori sunt, unica torculari solere ad reprimenda valores exsistentes; clavium iunctura ponens; ex manuali plura discere placet.
Wiring Diagram STC 9200
2020 Nova Wiring Diagram STC 9200 temperatura moderatoris

- Portus 1#: Viva wiring ex potestate initus erit output ad onera ex aliis portibus (#2/3/4) si condiciones perventum est, Periculosum est si filum iniuriae coniungas.
- port 2:
- port 3#: Nullam ad wiring defluentem unitatis evaporatorem;
- port 4#: Nullam pro Fan output;
- port 5 # & 6#: input potestas pro STC-9100 operandi, nullum opus est vivo vel nulla distinguere;
- port 7#: The NTC Sensor for metiendis cella temperies;
- Portus VIII #: Co-punctum pro duali temp NTC Sensor;
- port 9#: The NTC Sensor metiendis instanti temperie defringentis unitatis in evaporatore;
- Exemplar-clavem: Mini USB sectam portum ad molem configurare moderatoris.

Munus Menu of STC-9200 Controller
2nd col. est Acronym munus Anglice
III, col. F est abbreviatio functionis;
Cate. | En | F | Officium | Min | Default | Max | Unitas | Menu Level | |
---|---|---|---|---|---|---|---|---|---|
Temp. | SET | F01 | SP (Temperate Set-Point) | LS | -5 | US' | °C | User Menu | |
HY | F02 | Temperature Hysteresis / Differentia Redi | 1 | 2 | 25 | °C | |||
US' | F03 | Superior modus for SP | LS | 20 | 50 | °C | Admin Menu | ||
LS | F04 | Lower terminus for SP | -50 | -20 | US' | °C | |||
AC | F05 | Mora Tempus est Compressor Mora tempus defrosting (modo scelerisque aeris modus) | 0 | 3 | 50 | Min | |||
Defr. | IDF | F06 | Defrost | Cycle / Intervallum Tempus | 0 | 6 | 120 | Hora | |
MDF | F07 | Tempus diuturnum | 0 | 30 | 255 | Min | |||
DTE | F08 | Subsisto Temperature | -50 | 10 | 50 | °C | |||
FDT | F09 | Aqua madens Tempus | 0 | 2 | 100 | Min | |||
TDF | F10 | Modus Defrosting: EL: defrost by electrica-heating; HTG: Defrost a scelerisque aerem | EL | EL | HTG | ||||
DCT | F11 | Modus computat defrost cyclus; RT: Cumulative time from controlers on; COH: Cumulativo tempore compressoris excitantis. | RT | RT | COH | ||||
DFD | F12 | Exhibe modum cum defrosting: RT: Sensorem locus temperatus ostendit; IT: Defrost sensorem temperatus ostendit (diuturna X min cum defrosting super) | RT | RT | IT' | ||||
Fan | FNC | F13 | Fan output modos cum FOT ≥ 0: CTR: Fan incipit a FOT, Desine by FST; ONcontinuus operatio nisi defrosting incipit; CN: FOD valorem sit seconds ad Fan incipit postea quam compressor incipit, Fan cessat si incipiunt defrosting. | CTR | CTR | CN | |||
FOT | F14 | Evaporator sensorem Temperature pro Fan Starts | -50 | -10 | FST | °C | |||
FOD | F15 | Tempus mora Fan incipit: FOD FOD valorem sit seconds ad Fan incipit ante quam compressor incipit; Fan subsisto si refrigerationem sistit. FOD >= 0 : The Fan was controller by FNC | -255 | 60 | 255 | S | |||
FST | F16 | Evaporator sensorem Temperature pro Fan Stops | FOT | -5 | 50 | °C | |||
Alarm | ALU | F17 | Locus sensorem Temperature ad Trigger Alarm | Superior modus | OMNIS | 50 | 50 | °C | |
OMNIS | F18 | Lower Low | -50 | -50 | ALU | °C | |||
ALD | F19 | Tempus mora | 0 | 15 | 99 | Min | |||
Calib. | OT | F20 | Calibration caliditas | -10 | 0 | 10 | °C |
Ut ac posuere tortor?
Locus temperatus definitum est ex "F1" ad "F1 + F2" (ex "SET" ad "SET + HY");
Eas in usore interface seu Admin interface sistere potes, infra est the modum administratoris.
- Intra Admin Interface: clavis et clavis [Down] simul pro 10s tene; videbis codice "F1" ("SET").
- Preme clavis ad valorem currentem reprimendum, et clavis [Dun] clavis vel [Up] ut valorem mutet;
- Preme [SET] clavem ut novas notitias servet, et ad indicem menu reducas, codicem "F1" ("SET") iterum videbis.
- Vertas ad "F2" ( "HY") codice impresso [UP] clavem.
Placere referat sectionem 4.1 in forma PDF pro "ponere modum usoris interface».
Quomodo configurare Defrosting
Haec unitas per tempus et Temperaturam regat defrosting.
- Temperatus Condition: evaporatio sensoris temperatus humilior est quam preset "defrosting Sistere temperatus" F8 (DTE)quod magnopere pertinet ne defrost.
- Tempus Conditio 1: real-time transit consectetur tempus F6 (IDF)modulus regularis ad omnes fere thermostates defringendas.
- Tempus Conditio 2: Si "ratio defrosting" accipias est calidum gas e contrario gyratorius compressor F10 = 1 (TDF= HTG), Compressor ultimam desinit momentum plus F5 (AC)quae est valor tutelae ut compressorem saepe startup evitet ac desinat.
Hoc video etiam in aliis linguis praesto esse voces, eam eligere e angulo dextro cornu inferioris video
Quomodo ad Evaporationem Fan?
Reprehendo the F15 (FOD) valorem prae aliis, ut infra mindmap ostendit.

User Manuale STC-9200 thermostat Ebook Download
- Versio Anglica User Manual pro PC: User Manuale STC-9200 thermostat.pdf
- Versione Anglica Quick Guide pro Mobile: Quick Start Guide of STC-9200 thermostat.pdf
STC 9200 user manual in Russian
регулятора температуры STC-9200 - раткое руководство пользователя.pdfSTC 9200 Thermostat user manual in Spanish
Manual de usuario de Termostato STC-9200 en español.pdfHaswill Electronics has usores manuales creavit secundum Elitech STC 9200idem tibi persuadere non possumus, si artificium tuum ab aliis fabricantibus ut sigma, sterownik, Kamtech, vel Finglai fiat.
STC-9200 Error Code
-
- E01 et E02 sensores mediocres temperaturas validas notitias obtinere non possunt, fortasse funis thermistoris aperta vel brevis est, E01 pro cella sensorem, E02 a sensorem defrosting;
- HHH/LLL code significat valorem sensorem temperaturae mensuratum ultra extensionem mensurabilem; obsecro invenire formulam a STC-9200 instruction.
- Ostentatio nictans non-subsisto (Number readout coruscans) significat cubiculum sensorem existere problema; deprehensa temperies instantis permissam latitudinem excedit; Quaeso reprehendo tuum compressor et mutare statum operantes, si opus est, fixa temp sensorem.
FAQ de Haswill Foedus Panel Thermostat
- Quomodo vitare moderatores emptionis inferioris temperaturae?
hic est simplex modus, qui scientiam professio non requirit. - Quam impetro pretium?
Preme bullam inquisitionis, et formam perficies, responsum erit paucis horis. - Celsius VS Fahrenheit; et intentione
Omnes nostri digitalis temperatus moderatoris defaltam in gradibus Celsii, et pars eorum in Fahrenheit praesto est cum quantitatibus ordinis minimis;
Praeter 220V AC (± 15%), hi moderatores electronici temperaturae etiam in promptu sunt 110V AC, 12V DC, 24V DC (110/24/12 Volts). - Parameter Comparatio
Catalogue decuriae Foederis digitalis temperatus moderatoris - sarcina
Vexillum involucrum onerare potuit 100 PCS / CTN digitales temperatus moderatoris. - Accessories
Monemus tibi emere partes 5% ~ 10% parces sicut clips et sensoriis ut truncus. - Warranty
Defectus unius anni (extensibilis) qualitatis warantia omnibus nostris moderatoribus, gratuitam reponendam crimen offeremus si defectus qualitas inveniatur. - Customization Service
Si non potes aptam temperiem moderatorem huius loci invenire, adiuvabimus ut eam ex nostris proventibus maturis existentibus excolat;
Gratias Sinarum in plena copia ligatorum industriae cognatae, thermostatae nostrae nativus magni pretii sunt et humilis;
the MOQ is usually from M pieces. non dubitant contact us ad officia customization.
an plures quaestiones? Click FAQs
Minimum ordo moles: CC USD
Ut unus e distributoribus Elitech, Haswill Electronics praebet versionem originalem Elitech Brand in pretio competitive.